Specification Guide

Project-specific spec language organized by CSI division, filtered to your project type, climate zone, and certification goals. Each section includes performance thresholds and copy-ready language for your outline specifications.

Outline specifications only — not a substitute for a complete project manual. Performance thresholds are sourced from IECC 2021, ASHRAE 90.1-2022, LEED v4.1, Phius 2024, and ENERGY STAR program requirements. Confirm applicability with your AHJ and any certification body before finalizing drawings.
Section:
Building type:
Division 01
General Requirements
Commissioning, construction waste management, IAQ management plan, energy documentation
SectionRequirementApplies to
01 91 13 — General Commissioning Fundamental building systems commissioning for all mechanical, electrical, and plumbing systems. LEED EA PrereqES Req
Owner shall retain a Commissioning Authority (CxA) independent of the design team. Cx scope to include: HVAC, plumbing, lighting controls, and building envelope (enhanced).
All
01 74 19 — Construction Waste Management Divert minimum 75% of construction and demolition waste from landfill by weight or volume. LEED MR Credit
Provide dedicated on-site sorting areas for wood, metal, drywall, cardboard, and concrete. Submit monthly waste diversion reports to the Owner.
All
01 57 19 — Temporary Environmental Controls — IAQ Implement SMACNA IAQ Guidelines for Occupied Buildings Under Construction, 2nd Ed., during all phases of interior rough-in and finish work. LEED EQ Credit
Protect duct openings from dust. Replace all filters prior to occupancy. Run HVAC for 14-day flush-out per LEED EQc3.2 if required.
All
01 35 29 — Energy Documentation Contractor to compile and submit energy documentation package to Owner at substantial completion including: equipment cut sheets with rated efficiencies, TAB report, CxA final report, and as-built thermal envelope summary.
Required for AIA 2030 reporting, LEED energy disclosure, and ENERGY STAR verification.
LEED EAAIA 2030
All
Outline spec language — Division 01
01 91 13 — GENERAL COMMISSIONING Engage a Commissioning Authority (CxA) independent of the design and construction teams at or before schematic design. CxA credentials: ASHRAE CPMP, ACG CxA, or equivalent. Cx scope: mechanical, electrical, plumbing, building envelope, lighting controls, and renewable energy systems. Deliverables: Owner's Project Requirements (OPR) at SD; Basis of Design (BoD) review at DD; Functional Performance Testing report at substantial completion; Final Cx Report within 60 days of occupancy. [LEED EA Prereq: submit CxA contract and scope to LEED reviewer at permit.] 01 74 19 — CONSTRUCTION WASTE MANAGEMENT Submit Construction Waste Management Plan to Owner within 30 days of NTP. Provide on-site sorting for: dimensional lumber, metals, drywall, cardboard, concrete/masonry, and mixed recyclables. Document diversion by weight with hauler receipts. Submit monthly diversion reports. Target: minimum 75% diversion from landfill by weight. [LEED MR Credit: maintain separate receipts per material category; document total tonnage disposed vs. diverted.] 01 57 19 — TEMPORARY IAQ MANAGEMENT Implement SMACNA IAQ Guidelines for Occupied Buildings Under Construction, 2nd Ed., throughout all phases of interior rough-in and finish work. Cover and protect all duct and grille openings from dust throughout construction. Replace all HVAC filters at substantial completion with final rated filters. [LEED EQ Prereq: document daily protection log; conduct 14-day flush-out per LEED EQc3.2 or third-party IAQ testing prior to occupancy — coordinate with CxA for flush-out HVAC scheduling.] 01 35 29 — ENERGY DOCUMENTATION At substantial completion, Contractor shall deliver an Energy Documentation Package including: (1) equipment cut sheets for all major energy-consuming systems with rated efficiencies highlighted; (2) TAB Report; (3) CxA Final Report; (4) as-built thermal envelope summary confirming installed R-values and air barrier continuity; (5) blower door and duct leakage test results signed by tester. [AIA 2030: include projected annual EUI and 25-year carbon projection. LEED EA: provide energy model update confirming as-built compliance.]
Division 03
Concrete — Slab, Foundations, and Vapor Control
Below-slab vapor barrier, slab insulation, and concrete mix requirements — referenced in IECC, Phius, and FORTIFIED
AssemblyCode / standard minimumAbove-code / cert targetNotes
03 30 00 — Concrete Slab on Grade IRC R506.2: 4" min. slab over compacted granular fill; vapor retarder Class II (6-mil poly) on ground below slab per IECC zones 1-8 10-mil or 15-mil poly Phius: 15-mil recommended Lap vapor retarder seams minimum 6", tape all seams and penetrations. Extend to foundation wall and seal — this is the most commonly missed detail. Slab cold joint at perimeter: thermal break required for Phius; R-10 min. edge insulation for Zones 4-8 (IECC).
03 30 00 — Concrete Mix Design Minimum 28-day compressive strength: 3,000 psi residential / 4,000 psi commercial slabs. W/C ratio ≤ 0.50 for exposed exterior. ACI 318 for structural. w/c ≤ 0.45 below grade Specify supplementary cementitious materials (SCM) for embodied carbon reduction: 20–40% fly ash or slag cement replacement. Reduces embodied carbon 15–35% with equivalent or improved long-term strength. [LBC Materials: verify fly ash source for Red List compliance — avoid Class C fly ash with high heavy metal content where LBC target is pursued.]
07 26 00 — Below-Slab Vapor Retarder ASTM E1745 Class A or B vapor retarder — permeance ≤ 0.1 perm. IECC requires vapor retarder directly below slab in all zones. Stego Wrap 15-mil or equiv. Phius: required continuous Place vapor retarder immediately below slab — not below gravel. This is the Building Science Corporation and DOE recommendation; placing below gravel allows moisture accumulation between gravel and barrier. Coordinate with foundation drain and waterproofing at perimeter.
03 15 00 / 07 21 00 — Below-Slab Insulation Zone 3: R-5 (2 ft perimeter) | Zone 4-8: R-10 (2–4 ft perimeter) — IECC prescriptive. Under-slab: optional per code in most zones. See project zone Phius: R-15 full under-slab typical For Phius and high-performance targets: specify continuous rigid insulation under full slab area (XPS or polyiso) in addition to perimeter. Typical: 2" XPS (R-10) under slab + 4" XPS (R-20) slab edge. Coordinate with slab thickness and structural bearing at interior footings.
Outline spec language — Division 03
03 30 00 — CAST-IN-PLACE CONCRETE (SLAB ON GRADE) Mix design: minimum 3,000 psi at 28 days (residential) / 4,000 psi (commercial floor slabs). Water-cementite ratio ≤ 0.50; ≤ 0.45 below-grade and exposed exterior. Specify 20–30% fly ash or slag cement replacement (ASTM C618 Class F fly ash or ASTM C989 Grade 100 slag) for embodied carbon reduction. Submit mix design with SCM source documentation 21 days prior to pour. 07 26 00 — BELOW-SLAB VAPOR RETARDER Vapor retarder: ASTM E1745 Class A, minimum 15-mil polyethylene (Stego Wrap 15-mil, Perminator 15-mil, or approved equal). Install directly below slab — not below granular fill layer. Lap seams minimum 6 inches; tape all seams, pipe penetrations, and column base penetrations with compatible tape. Extend up foundation wall minimum 6 inches; seal to foundation with compatible sealant at perimeter. Repair any punctures before pour with tape patch minimum 12 inches larger than damage. 07 21 00 — BELOW-SLAB AND PERIMETER INSULATION [Zone 4-8] Slab edge: extruded polystyrene (XPS), ASTM C578 Type IV, [R-value per project zone], installed vertically at perimeter from top of slab to frost depth or 4 feet minimum. Thermal break required — slab must not bear directly on foundation wall without insulating break. [Phius target: XPS R-10 (2") under full slab area in addition to perimeter, coordinate with structural footing bearing.] Protect all below-grade XPS with concrete board or protection board at backfill.
Division 06
Wood and Framing — Structural Panels and Mass Timber
Framing lumber, structural panels, mass timber options, and wildfire-relevant framing details
SystemCode minimumAbove-code / recommendedNotes
06 10 00 — Framing Lumber Structural grade lumber per IBC Table 2306.1 / IRC R602. Grade stamp required. Moisture content ≤ 19% at time of enclosure per IRC R318. LEED MR: FSC certified preferred Specify FSC-certified lumber (Forest Stewardship Council) for LEED MR Credit and general sustainability preference. Require grade stamp documentation at inspection. Engineered lumber (LVL, LSL, I-joists) for long spans — reduced waste, no old-growth, dimensional stability. [LBC: FSC certification required for all wood products.]
06 16 00 — Sheathing (structural panels) APA-rated OSB or plywood: sheathing per IBC Table 2308, nailing per table. Exposure 1 minimum for wall sheathing. Exterior-rated (Exposure 1 or better) required where sheathing may be exposed to weather during construction. ZIP System or taped sheathing ZIP System integrated sheathing + air barrier (or equivalent taped structural sheathing) eliminates separate housewrap layer and reduces penetration points. Strongly preferred for Phius, ENERGY STAR, and high-performance air barrier targets. Tape all panel joints with manufacturer-specified tape at installation. [FORTIFIED: structural sheathing nailing schedule typically governs over code minimum in wind design areas — verify with IBHS evaluator.]
06 17 00 — Prefabricated Structural Wood I-joists and LVL: design per manufacturer's Span Tables. Engineered wood per ICC evaluation reports. LEED MR: FSC engineered wood credit-eligible Engineered wood products (EWP) reduce overall lumber volume 10–15% vs. dimensional framing. Factory-manufactured means tight tolerances, reduced callbacks. Specify factory-drilled knockout locations for MEP to reduce field drilling — coordinate with MEP team at SD. Web stiffeners at bearing points — specify in framing documents.
06 17 53 — Mass Timber (CLT/GLT) CLT: ANSI/APA PRG-320. GLT (glulam): AITC 117 / ANSI 117. Fire resistance per IBC Table 722.7 — exposed mass timber permitted in Type IV construction (IBC 2021). LEED MR: responsible sourcingAIA 2030: biogenic carbon Mass timber (CLT, NLT, GLT) sequesters biogenic carbon — report as negative embodied carbon in AIA 2030 tracking. IBC 2021 Type IV construction categories (A/B/C) allow exposed mass timber in taller structures without encapsulation in Type IV-A. Coordinate fire design early — exposed CLT must meet IBC char layer requirements. Require EPD for all CLT/GLT panels. Source domestically for supply chain reliability (PNW primary production region).
Outline spec language — Division 06
06 10 00 — ROUGH CARPENTRY (FRAMING LUMBER) Lumber: structural grade per species and use, grade-stamped per WWPA or NLGA grading rules. Moisture content: ≤ 19% at time of enclosure (IRC R318). FSC-certified lumber required [or preferred] — provide chain-of-custody documentation from supplier. No old-growth lumber. Dimensional lumber: No. 2 minimum for stud framing; No. 1 or LVL at bearing locations per drawings. Preserve existing trees in immediate vicinity of structure — coordinate laydown areas with Owner. 06 16 00 — SHEATHING Wall sheathing: APA-rated OSB, 7/16" minimum, Exposure 1, with APA performance category per structural drawings. Nailing: 8d common at 6" o.c. edges / 12" o.c. field (unless noted otherwise on structural for shear wall zones). Air barrier integration: apply manufacturer-specified tape to all panel joints, window and door rough openings, and penetrations within 48 hours of installation. [ZIP System: use ZIP System tape at all seams; apply roller per manufacturer instructions. Field cuts: apply flashing tape immediately.] 06 17 53 — STRUCTURAL COMPOSITE LUMBER (where applicable) LVL and LSL beams: per manufacturer Span Tables; ICC evaluation report to be submitted at permit. I-joists: APA PRI-400; blocking required at all bearing points, end walls, and web stiffeners at point loads — indicate on structural. Factory knockout locations for MEP to be coordinated with mechanical, electrical, and plumbing drawings at DD — provide shop drawings for review. [Mass timber: CLT panels per ANSI/APA PRG-320; require EPD and FSC or PEFC certification; submit EPD to Owner for AIA 2030 / embodied carbon tracking.]
Division 07
Thermal and Moisture Protection
Insulation, air barrier, vapor retarder, roofing — performance values shown by IECC climate zone
Load a project with ZIP code to see zone-specific R-value and U-factor requirements highlighted for your climate.
AssemblyIECC 2021 Code Min.Above-code / Cert targetNotes
07 21 00 — Above-grade Wall Insulation Zone 1-2: R-13 | Zone 3-4: R-20 | Zone 5-6: R-20+5ci | Zone 7-8: R-20+10ci See project zone Phius: varies by HDDLEED EA: 5% above code Continuous insulation (ci) outboard of studs avoids thermal bridging. Required for Phius and LEED above-code paths in Zones 5+.
07 21 00 — Attic / Roof Insulation Zone 1-2: R-38 | Zone 3-4: R-49 | Zone 5-8: R-49 to R-60 See project zone Phius: R-60+ typicalES: R-49 min Zones 5+ For unvented roofs, confirm vapor control strategy per IRC R806.5 or IECC climate zone vapor retarder class requirements.
07 21 00 — Slab Edge / Below-grade Zone 1-2: none | Zone 3: R-5 (2 ft) | Zone 4-8: R-10 (2-4 ft) See project zone Phius: R-15+ typical Slab edge thermal bridging is the most commonly missed detail. Thermal break required at all slab-to-wall connections for Phius.
07 27 00 — Air Barrier System Air leakage ≤ 0.40 CFM75/ft² of building envelope area (IECC C402.5 commercial) | 3 ACH50 (residential) ≤ 0.10 CFM75 (LEED enhanced) Phius: ≤ 0.06 ACH50LEED: enhanced EA option Air barrier must be continuous and co-planar. Specify: wrap type (fluid-applied or sheet), tape at all penetrations and joints, testing protocol (ASTM E779 or ASTM E1827), and test timing (pre-drywall).
Phius certification requires third-party blower door testing. ENERGY STAR requires HERS rater or equivalent.
07 46 00 / 07 52 00 — Roofing SRI ≥ 64 (steep-slope) or ≥ 82 (low-slope) — IECC cool roof requirements vary by zone LEED SS: SRI ≥ 82 (low), ≥ 39 (steep) For wildfire zones: Class A roof assembly required for IBHS FORTIFIED and Wildfire Prepared Home. No wood shingles or shakes regardless of treatment.
Outline spec language — Division 07 (zone-specific values filled from project)
07 21 00 — THERMAL INSULATION (ABOVE-GRADE WALL) Insulation: [zone-specific R-value — load a project to fill]. [If continuous insulation required: specify closed-cell spray polyurethane foam (ccSPF, ASTM C1029 Type II) or polyisocyanurate rigid board (ASTM C1289) outboard of framing. Minimum R-value per IECC Table R402.1.2. Install in continuous layer with no gaps at fasteners or Z-channels.] Batt insulation: friction-fit to fill cavity 100% — no voids, no compression. Third-party inspection required prior to insulation cover at framing rough-in stage. 07 21 00 — THERMAL INSULATION (ATTIC/ROOF) Blown-in attic insulation: [zone-specific R-value] minimum at finished depth. Install baffles at all eave vents to maintain ventilation channel minimum 1". Depth markers every 50 sq ft; confirm installed R-value with job worksheet at substantial completion. [Unvented assemblies: verify vapor control strategy per IECC climate zone — foam at roof deck preferred for mixed and cold climates.] 07 27 00 — AIR BARRIERS, AIR SEALING, AND VAPOR RETARDERS Air leakage performance target: [≤ 3 ACH50 code / ≤ 0.60 ACH50 ENERGY STAR / ≤ 0.06 ACH50 Phius]. Specify one primary air barrier strategy: (A) fluid-applied membrane on sheathing; (B) integrated sheathing system (ZIP System or equivalent); or (C) interior drywall with careful sealing at all penetrations and plates. Tape or flash all window and door rough openings, rim joists, penetrations through top and bottom plates, and electrical/plumbing penetrations. Test per ASTM E779 at pre-drywall stage — notify testing agent minimum 48 hours in advance. 07 46 00 / 07 52 00 — ROOFING Specify roofing material, SRI, and fire rating on drawings. [Cool roof requirement: SRI ≥ 82 low-slope, ≥ 39 steep-slope for LEED SS Credit.] [Wildfire/FORTIFIED zones: Class A fire-rated assembly required — no wood shingles or shakes regardless of fire retardant treatment. Impact-resistant Class 4 shingles required for IBHS FORTIFIED in hail exposure zones.] Ice and water shield: ASTM D1970, minimum 24" from eave or to point 24" inside interior wall, whichever is greater (Zones 5-8 minimum).
Division 08
Openings — Windows and Doors
U-factor, SHGC, and structural performance requirements by climate zone and certification
Load a project with ZIP code to see climate-zone-specific window performance targets.
ComponentIECC 2021 Code Min.Above-code / Cert targetNotes
08 50 00 — Windows (all orientations) Zone 1-2: U-0.40 SHGC-0.25 | Zone 3-4: U-0.32 SHGC-0.25 | Zone 5-8: U-0.30 SHGC 0.40 See project zone Phius: triple-pane Zones 5+LEED EA: 5% above code model Specify per NFRC 100 ratings. Require NFRC label on all units. Coordinate SHGC by orientation: see Design Strategies page for zone-specific SHGC targets.
Passive solar design (south-facing high-SHGC) can offset heating loads in Zones 4-8. Model in energy software before specifying.
08 50 00 — Windows (wind/storm zones) ASTM E1886 / ASCE 7 design wind pressure per jurisdiction Impact-rated DP-50+ FORTIFIED req. FORTIFIED Silver and Gold require impact-rated windows and doors or rated shutters meeting ICC 500 or ASTM E1886/E1996. Specify DP rating at the time of design using ASCE 7 local wind speed map.
08 11 16 — Exterior Doors Zone 1-4: U-0.20 (insulated) | Zone 5-8: U-0.17 ES: U-0.17 all zonesFORTIFIED: impact-rated or shuttered Specify door air leakage ≤ 0.50 CFM/ft perimeter (exterior doors), ≤ 0.30 sliding doors. Require AAMA 101/NFRC ratings on submittals.
08 31 00 — Access Doors + Attic Hatches All hatches to conditioned space: U-factor equivalent to surrounding assembly per IECC ES: insulated pull-down stair cover required Attic access covers are a common air leakage failure point. Require gasketed, rigid-insulated panel or Access Dome at all pull-down stairs. Test at framing rough-in.
Outline spec language — Division 08
08 50 00 — WINDOWS Performance: [zone-specific U-factor and SHGC — load a project to fill]. All windows NFRC-labeled; include NFRC certification label in submittals. Glazing specifications to be confirmed per orientation: south-facing, east/west, and north have different optimal SHGC values — see Design Strategies page zone SHGC table. [Phius: triple-pane required in Zones 5+; provide PHPP window entry data (Uw, g-value) on submittals.] [FORTIFIED Silver/Gold: impact-rated per ICC 500 / ASTM E1886/E1996, or rated storm shutters — specify DP rating from ASCE 7 wind speed for site.] Provide window schedule on drawings with unit sizes, rough opening dimensions, U-factor, SHGC, and DP rating for each unit type. 08 11 16 — EXTERIOR DOORS Minimum performance: [Zone 1-4: U-0.20 / Zone 5-8: U-0.17]. Air leakage: ≤ 0.50 CFM/ft perimeter at 0.30 in. w.g. test pressure (AAMA 107). Sliding glass doors: ≤ 0.30 CFM/ft. Require AAMA or NFRC ratings on submittals. Weatherstripping: replaceable compression type at all exterior door perimeters; continuous threshold at door bottoms — no visible light gap. [FORTIFIED: same impact-rating requirement as windows applies to all exterior doors. Garage doors: require AAMA 512 rated units in wind design areas.] 08 31 00 — ATTIC ACCESS AND PULL-DOWN STAIRS All pull-down attic stair units: insulated cover assembly, minimum R-value equivalent to surrounding assembly. Gasketed rigid panel type (Access Dome, Battic Door, or equivalent) preferred — avoids foam deterioration of roll-type covers. At attic hatch (no pull-down stair): rigid insulated cover, minimum 2" rigid foam, gasketed with weatherstripping. Inspect and test per ENERGY STAR Thermal Enclosure Checklist at framing rough-in stage.
Division 09
Finishes and Indoor Air Quality
Low-VOC paints, adhesives, flooring — requirements for LEED EQ, WELL, and general best practice
Product categoryVOC limitStandard / certificationNotes
09 90 00 — Paints and Coatings Interior: ≤ 50 g/L flat, ≤ 150 g/L non-flat (LEED) | Exterior: ≤ 100 g/L flat, ≤ 200 g/L non-flat LEED v4.1 EQ Credit Reference SCAQMD Rule 1113 and CARB Suggested Control Measure for architectural coatings. Require product data sheets confirming VOC content at submittal.
09 20 00 — Adhesives and Sealants Indoor adhesives: ≤ 70 g/L (SCAQMD Rule 1168) | Architectural sealants: ≤ 250 g/L LEED v4.1 EQ Credit Applies to adhesives, sealants, primers, and sealant primers applied to the interior of the building envelope. Coordinate with Division 07 air barrier sealants.
09 60 00 — Flooring (carpet) Carpet: CRI Green Label Plus | Carpet cushion: CRI Green Label | Adhesive: ≤ 50 g/L LEED v4.1 EQ Credit All carpet and adhesive to have CRI Green Label Plus certificate. Submit certificate at procurement.
09 60 00 — Flooring (hard) Composite wood: California 93120 ATCM Phase 2 compliant (CARB) | FloorScore certified preferred LEED v4.1 EQ Credit Formaldehyde emissions from composite wood products (particleboard, MDF, plywood) to meet CARB Phase 2 limits. Require manufacturer HPD or declare compliance. CARB Phase 2 is now federal via EPA TSCA Title VI.
09 81 00 — Acoustic Insulation / Batt Mineral wool or fiberglass (formaldehyde-free preferred) LEED EQ Formaldehyde-free mineral wool batt preferred at interior partitions for IAQ and acoustic attenuation. Coordinate with fire-rated assembly listings.
Outline spec language — Division 09 (Finishes + IAQ)
09 90 00 — PAINTS AND COATINGS All interior paints, stains, and coatings: VOC content ≤ 50 g/L (flat) / ≤ 150 g/L (non-flat) per SCAQMD Rule 1113 and CARB SCM. All exterior coatings: ≤ 100 g/L (flat) / ≤ 200 g/L (non-flat). Require product data sheets confirming VOC content at submittal stage — not just manufacturer's general literature. [LEED v4.1 EQ Credit: VOC content verified per SCAQMD Rule 1113; submit product list with VOC values for each coating used at each surface type. GreenSeal GS-11 certified products preferred.] 09 20 00 — GYPSUM BOARD AND JOINT TREATMENT Gypsum board: ASTM C1396 standard; use mold-resistant (Type X or MR) in all bathrooms, utility rooms, and other humid-area locations per IRC R702.3. Joint compound: low-VOC (≤ 50 g/L) — note that pre-mixed joint compound can have high VOC content; verify and specify. [Embodied carbon: gypsum board contains significant embodied carbon — specify products with EPDs for AIA 2030 tracking where contractor can source competitively.] 09 60 00 — FLOORING Carpet: CRI Green Label Plus certified. Carpet cushion: CRI Green Label certified. Adhesive: ≤ 50 g/L. Require CRI certificate at procurement submittal. Composite wood flooring (hardwood, bamboo, laminate): California ATCM Phase 2 / EPA TSCA Title VI compliant — CARB Phase 2 formaldehyde emission limits. FloorScore-certified products preferred. Require HPD (Health Product Declaration) or Declare label from manufacturer at submittal. [LBC Materials Petal: all composite wood must be certified compliant; prohibit urea-formaldehyde binders in all wood products.] 09 81 00 — ACOUSTIC INSULATION Interior partition batt: mineral wool (ASTM C665 Type I) or fiberglass (formaldehyde-free preferred) at all party walls, corridor walls, and bedroom demising partitions. Install full-height cavity fill — 3.5" batt at 2x4 framing minimum, no air gaps at top and bottom plates. Coordinate acoustic batt specification with fire-rated assembly listings (UL, GA) — some fire-rated assemblies require specific products. STC ratings per drawings and specifications for party walls and noise-sensitive spaces.
Division 22
Plumbing — Water Efficiency
Fixture flow rates, hot water delivery, and water metering requirements
FixtureEPA WaterSense / IPC 2021LEED WE targetNotes
22 40 00 — Lavatory Faucets ≤ 0.50 GPM (WaterSense private) | ≤ 0.50 GPM (LEED indoor water prereq) 0.35 GPM LEED WE Credit Require EPA WaterSense label on all lavatory and kitchen faucets. Metered faucets in commercial: ≤ 0.20 GPM.
22 40 00 — Showerheads ≤ 1.75 GPM (WaterSense) | ≤ 2.0 GPM (IPC 2021 base) 1.50 GPM LEED WE Credit WaterSense label required. Multi-port showerheads: combined flow ≤ 1.75 GPM per WaterSense. Coordinate with water heater sizing for low-flow fixtures.
22 40 00 — Water Closets ≤ 1.28 GPF (WaterSense) | ≤ 1.28 GPF (IPC 2021) 1.0 GPF dual-flush LEED WE Credit Dual-flush toilets (0.8/1.28) count at blended rate for LEED calculations. WaterSense-labeled required for residential ENERGY STAR.
22 33 00 — Domestic Water Heating Heat pump water heater (HPWH) preferred | EF ≥ 2.0 (UEF 0.95+) for electric units LEED EAPhius: HPWH required Zones 3+ Heat pump water heaters (HPWH) provide 2–4x efficiency of resistance. ENERGY STAR-certified HPWHs qualify for federal tax credit (IRA Section 25C). Location: conditioned or semi-conditioned space only.
Avoid locating HPWH in mechanicals rooms adjacent to bedrooms — unit generates sound and heat draw. Best location: garage, utility room, or basement.
22 11 16 — Hot Water Distribution Pipe insulation ≥ R-4 for first 8 ft from water heater | IECC Table C403.2.10 LEED WE Credit Demand recirculation (sensor-activated) preferred over continuous recirculation for LEED. Pipe insulation to full run for Phius. Measure fixture delivery time — maximum 10–15 seconds for WaterSense certification path.
Outline spec language — Division 22 (Plumbing)
22 40 00 — PLUMBING FIXTURES All lavatory faucets: EPA WaterSense labeled, maximum 0.50 GPM (private) / 0.20 GPM (metered, commercial). All showerheads: WaterSense labeled, maximum 1.75 GPM; multi-port showerheads measured as combined flow. All water closets: WaterSense labeled, maximum 1.28 GPF; dual-flush (0.8/1.28 GPF) preferred. Specify fixture model numbers on plumbing fixture schedule on drawings — do not allow contractor substitution of unlabeled units. Require WaterSense label documentation at submittal. 22 33 00 — DOMESTIC WATER HEATERS Heat pump water heater (HPWH) required for all electric water heating. Minimum UEF 3.0 (≥ 40-gallon units) or per ENERGY STAR certification list. Install in conditioned or semi-conditioned space with minimum 700-1,000 cu ft of air volume; or provide dedicated outdoor air duct kit per manufacturer. Do not locate adjacent to bedroom walls — HPWH operating sound level 45–50 dB. Drain pan and drain to floor drain required. [IRA Section 25C: ENERGY STAR-certified HPWH qualifies for 30% federal tax credit up to $600. Inform owner at equipment selection.] [Phius: HPWH required in all climate zones with electric domestic hot water. Natural gas: high-efficiency condensing unit (EF ≥ 0.80) only.] 22 11 16 — HOT WATER DISTRIBUTION PIPING Insulate all hot water supply piping minimum R-4 (1" foam pipe insulation) for full run length — not just first 8 feet. Demand-controlled recirculation preferred over continuous: sensor-activated or timer-controlled at fixture; avoids continuous heat loss from recirculation. [LEED WE Credit: measure delivery time — maximum 10-15 seconds from any fixture to meet WaterSense hot water delivery criteria.] Pipe insulation at all accessible locations: verify installation before closing walls.
Division 23
HVAC — Heating, Ventilation, and Air Conditioning
Equipment efficiency, ventilation rates, and IAQ requirements by building type and certification
SystemCode minimumRecommended / cert targetNotes
23 81 00 — Heat Pumps (air-source) SEER2 ≥ 14.3 South / ≥ 13.4 North (2023 DOE standard) | HSPF2 ≥ 7.5 SEER2 ≥ 18 ES: SEER2 ≥ 15.2 / HSPF2 ≥ 7.8Phius: size per PHPP Cold-climate heat pumps (CCHP): rated performance at 5°F required for Zones 5+. Specify rated capacity at +17°F and +5°F on equipment schedule. Ducted vs. ductless based on floor plan. Qualify for IRA Section 25C credit if SEER2 ≥ 15.2.
23 74 00 — Energy Recovery Ventilation (ERV) ASHRAE 62.2 (residential): 0.01 CFM/ft² + 7.5 CFM/person | IECC C403.3 (commercial): per occupancy SRE ≥ 75% Phius: SRE ≥ 75% (PHIUS ERV)LEED EQ: enhanced ventilation ERV required for all Phius projects. Recommended for LEED enhanced ventilation path. Size per ASHRAE 62.2 Manual J load or CxA calculation. Locate supply air away from return air to prevent short-circuiting. MERV-13 filtration on supply air minimum.
HRV vs. ERV: ERV transfers moisture — preferred in mixed and humid climates (Zones 1-4). HRV does not transfer moisture — preferred in cold-dry climates (Zones 5-7).
23 31 00 — Ductwork Duct leakage ≤ 4 CFM25/100 ft² (residential IECC 2021 total) | Commercial: per ASHRAE 90.1 ≤ 2 CFM25 ES: ≤ 4 CFM25 total leakagePhius: interior ducts only All supply and return ducts to be within conditioned space where possible. If attic or crawl space located: must be thoroughly sealed and tested. Phius: all ductwork inside pressure boundary preferred. Duct blaster test at rough-in.
23 09 00 — Controls and Thermostats IECC: programmable thermostat or equivalent | ASHRAE 90.1: occupancy sensors in applicable spaces LEED EQ: individual thermal comfort controlsES: smart thermostat Smart thermostats (Wi-Fi enabled, learning capable) qualify for utility rebates in most states and are required for ENERGY STAR Homes v3.2 where provided. Demand control ventilation (DCV) required for commercial >500 sqft per person.
Outline spec language — Division 23 (HVAC)
23 81 00 — HEAT PUMPS (AIR-SOURCE) Equipment performance: minimum SEER2 [15.2 ENERGY STAR / 18 recommended / per project cert goal], HSPF2 ≥ 7.8. [Zones 5-7: cold-climate heat pump (CCHP) required — rated heating capacity at +5°F on equipment schedule. Specify rated capacity at +17°F and +5°F on equipment submittal.] Size per ACCA Manual J load calculation — do not exceed 115% of calculated peak load. Provide load calculation signed by licensed engineer or certified HVAC designer at permit. Equipment selection from AHRI certified directory. [Phius: size per PHPP heating and cooling load outputs.] 23 74 00 — ENERGY RECOVERY VENTILATION (ERV / HRV) Ventilation design: per ASHRAE 62.2-2022 (residential) or 62.1-2022 (commercial). Minimum airflow: 0.01 CFM/ft² + 7.5 CFM/person. [Climate recommendation: ERV (moisture transfer) for mixed and humid climates Zones 1-4; HRV (sensible only) for cold-dry climates Zones 5-7.] ERV/HRV unit: sensible recovery efficiency (SRE) ≥ 75% at ASHRAE standard test conditions. [Phius: Phius-certified component required — see phius.org component list.] MERV-13 filters on supply air minimum. Unit location: inside pressure boundary. Separate supply and return locations — minimum 10 ft apart to prevent short-circuit. Balanced flow (+/- 10% of nominal). Test airflows and document in Cx report. 23 31 00 — DUCTWORK AND AIR DISTRIBUTION Duct leakage performance: ≤ [4 CFM25/100 ft² total to outside — ENERGY STAR / 2 CFM25 — above code target]. All duct connections mechanically fastened and sealed with mastic sealant or UL 181 tape — no cloth duct tape. Insulate all ducts in unconditioned spaces: R-8 supply, R-6 return (IECC). [Phius: all ductwork must be inside pressure boundary — no ducts in attic, crawl space, or garage.] Test per ASTM E1554 at rough-in — before sheetrock. Record test results. Confirm all registers, boots, and diffusers sealed airtight at openings before final inspection.
Division 26
Electrical — Lighting, Metering, and EV Readiness
Lighting power density, controls, submetering, and EV charging rough-in requirements
SystemCode minimumAbove-code / cert targetNotes
26 51 00 — Interior Lighting IECC C405 LPD: varies by space type. Residential: all fixed lighting to be high-efficacy (≥ 45 lumens/watt) ≥ 60 lm/W all LED LEED EQ: enhanced LPD + controls All luminaires to be LED. Prohibit incandescent and T8 fluorescent — both are phased out under DOE January 2023 rule. Specify CRI ≥ 80 minimum, CRI ≥ 90 in residential living and commercial food service.
26 09 23 — Lighting Controls IECC 2021: occupancy sensors required in classrooms, conference rooms, offices < 250 ft², copy rooms, locker rooms, storage rooms, utility rooms LEED EQ: individual and group occupancy controls Daylight-responsive controls required by IECC in spaces with fenestration > 150 sqft within 15 ft of windows. Provide dimming controls where LEED enhanced lighting controls credit is pursued.
26 27 26 — Wiring Devices — EV Readiness NEC 625.2 requires EV capable spaces (conduit only) for new residential under 2023 NEC. Some jurisdictions: minimum 1 EVSE or conduit per unit Level 2 (240V / 30A) LEED LT: EV charging infrastructure credit Provide minimum 1 dedicated 240V / 50A circuit rough-in per garage bay in residential. Multifamily: 20% of parking spaces EV-capable per LEED LT Credit. Commercial: 2–5% EVSE depending on parking count. Coordinate panel sizing at permit.
26 09 13 — Power Metering Commercial: IECC C405.13 submetering for lighting, HVAC, and process loads > 100 kW LEED EA: advanced energy metering creditAIA 2030: actual EUI tracking For AIA 2030 reporting and LEED advanced energy metering: install REVENUE-GRADE meters at the building level and for each enduse > 10% of projected energy consumption. Trending data to BAS at 15-minute intervals minimum.
Outline spec language — Division 26 (Electrical)
26 51 00 — INTERIOR LIGHTING All permanently installed luminaires: LED, CRI ≥ 80 minimum (CRI ≥ 90 in residential living areas, food service, and retail). Color temperature: 2700-3000K residential / 3000-3500K commercial office and retail (confirm with Owner at SD). Prohibit incandescent and fluorescent (T8 and compact) in new construction — DOE 2023 prohibition effective January 2023. Minimum efficacy: 60 lumens per watt at fixture. Provide photometric calculations confirming foot-candle levels at work surfaces per IES guidelines for occupancy type. [LEED EQ: provide enhanced lighting controls documentation — individual task controls and group occupancy controls per LEED EQ Credit.] 26 09 23 — LIGHTING CONTROLS Occupancy/vacancy sensors required at: all individual offices, conference rooms, break rooms, restrooms, storage rooms, and utility spaces. Daylight-responsive controls (dimming) required in spaces with fenestration > 150 sq ft within 15 ft of windows (IECC C405). Specify sensor coverage zones — no dead zones in any controlled space. [LEED EQ: individual dimming controls at all workstations plus group occupancy sensors for enhanced lighting credit.] All sensors: manual-on / auto-off preferred for offices (vacancy sensor) — reduces wasted energy vs. auto-on/auto-off. 26 27 26 — EV CHARGING INFRASTRUCTURE Residential (single-family and multifamily): minimum one dedicated 240V / 50A branch circuit rough-in (conduit + wire + breaker, NEMA 14-50 receptacle) per garage bay. [Multifamily: 20% of total parking spaces per LEED LT EV Credit; minimum per NEC 625 / local amendment.] Commercial: [2-5% of spaces with EVSE per LEED; verify local AHJ requirement]. Coordinate panel capacity at permit — EV load must be included in service calculation. Provide J1772 Level 2 EVSE (or roughed conduit for future EVSE) at designated spaces; stub conduit to panel with circuit breaker space reserved. 26 09 13 — POWER METERING AND SUBMETERING Building-level revenue-grade meter: required for all commercial buildings. Submetering: per IECC C405.13 for buildings with lighting, HVAC, or process loads > 100 kW — separate meters at each major end use > 10% of total energy. [LEED EA Advanced Energy Metering: revenue-grade meters for whole building and each end use > 10%, trending to BAS at 15-minute intervals minimum.] [AIA 2030 reporting: whole-building meter data required for annual EUI reporting through AIA 2030 DDx.] Specify meter type, communication protocol (BACnet, Modbus), and data integration path to building automation system.